Multifunctional transducer MFU 12/14

 SAR 78330 78340 object_image_64221imagemain_en
 ANW 78330 78340
Data sheet multifunctional transducer MFU 12/14
AFRISO Data sheet multifunctional transducer MFU 12/14

Versions

Part no. Remember
Transducer MFU 12 2 voltage-free changeover contacts 53722
Transducer MFU 14 4 voltage-free changeover contacts 53723
Software MFU 03-S with interface cable and USB adapter 53724

Blue part no. = in-stock items

Description Format Language Download / Link
Data sheet multifunctional transducer MFU 12/14 Data sheet PDF
AFRISO Data sheet multifunctional transducer MFU 12/14
Current up to 20 mA (also bipolar), voltage up to 10 V (also bipolar) or a three-wire technology potentiometer are possible input signals. In addition, a supply for 2-wire or 3-wire transmitters is integrated. The inputs are galvanically isolated from the voltage and the outputs. The two analogue outputs can be used simultaneously.
Display
Multi-line LCD,
42 x 64 pixels,
Multicolour backlight,
Backlight can be switched off
Range
0 to 9,999 digits,
Start and end values configurable as required,
Free scaling unit,
3 languages (German, English, French)
Accuracy
± 0.2 % of maximum value
Resolution
Inputs:
13 Bit
Outputs:
10 Bit
Inputs
Current:
Max. -20.4/+20.4 mA, adjustable as required
Voltage:
Max. -10.2/+10.2 V, adjustable as required
Potentiometer:
0.1/100 kOhm, adjustable as required
Transmitter supply:
DC 19.5 – 24.5 V
Analogue output 1 (current)
Max. 0/4–20.4 mA, adjustable as required
Galvanically isolated from input
Analogue output 2 (voltage)
Max. 0/2–10.2 V, adjustable as required
Galvanically isolated from input
Switching outputs
MFU 12:
2 voltage-free changeover contacts
MFU 14:
4 voltage-free changeover contacts
Configurable as required Configurable functions: energising/de-energising, hysteresis, window or trend function, selectable delays for energising/de-energising, configurable functions: energising/de-energising, hysteresis, window or trend function, selectable delays for energising/de-energising
Contact rating:
Max. AC 250 V
Linearisation
Via 24 free x/y points on characteristic curve, characteristic curve mode table, cylinder, sphere
Additional functions
Alarm message in the case of missing or defective sensor, Zoom function, spreading, inverted mode, trend indication, teach functions, automatic or manual simulation mode, Locking of parameters / editing lock, Programming interface
Supply voltage
AC 50 – 253 V
DC 20 – 253 V
Housing
DIN rail housing
W x H x D:
33 x 110 x 128 mm
Screw terminals removable

Options

  • Programming software MFU 03-S (Win XP, Vista, 7) with interface cable and USB adapter
  • Device with identical functions, but for temperature inputs (Pt100, Pt1000, Ni1000 and thermocouples)