Alarm unit AG 10 Ex

 ILL 77210  ILL 77210
 ILL 77210 <div class="gallery-information"> <b>Legend:</b> <ol> <li>Combined alarm light and horn</li> <li>Cylinder battery</li> <li>Pressure gauges with electrical contacts</li> </ol> </div>
 VOR 77210 object_image_95197imagemain_en
 SAL 77210
 ILL 77210
Data sheet Alarm unit AG 10 Ex
AFRISO Data sheet Alarm unit AG 10 Ex

Versions

Part no. Remember
Alarm unit AG 10 Ex 67000

Blue part no. = in-stock items

Description Format Language Download / Link
Data sheet Alarm unit AG 10 Ex Data sheet PDF
AFRISO Data sheet Alarm unit AG 10 Ex
Alarm unit AG 10 Ex Operating instructions PDF
AFRISO Alarm unit AG 10 Ex
Alarm unit AG 10 Ex Declaration of Conformity PDF
AFRISO Alarm unit AG 10 Ex

The system consists of one or several pressure contacts (connected in series), a control unit (alarm unit AG 10 Ex) and, if required, an additional alarm unit. If several contacts are to be monitored, the corresponding number of electrical contacts can be connected in series and monitored by a single alarm unit. It is also possible to connect a separate alarm unit for each measuring point. An alarm is triggered when the contact opens. An event reporting system can be connected to the relay output of the alarm unit for remote monitoring.

The alarm signal is generated by a pressure gauge with an electrical contact. The alarm threshold can be set to any value from 5 to 95 % of the range by means of the contact arm of the pressure gauge. A green LED indicates normal operation. In case of a power outage, the device does not generate an alarm signal; when power becomes available again, the unit immediately resumes operation. If, in the meantime, the gas pressure has fallen below the set limit, an alarm signal is generated. In the case of an alarm, the red LED lights up; in addition, the system generates an audible alarm. The audible alarm can be acknowledged. The red LED remains lit. The alarm can also be configured for fail-safe mode so that an alarm can also be triggered in the case of a power outage. Proper operation of the system can be checked at all times by means of pressing the Test key. If this button is pressed, the system generates an alarm, i.e. the red LED lights up and the audible alarm sounds.

Operating temperature range
Ambient:
-20/+50 °C
Supply voltage
AC 230 V ± 10 %
Power input
5 VA
Switching input
Voltage-free connection, e.g. Bourdon tube pressure gauge with magnetic spring contact
Probe circuit
Intrinsically safe
Maximum values:
U0 = 16.8 V
I0 = 57 mA
P0 = 240 mW
C0 = 180 nF for IIC, 675 nF for IIB
L0 = 1 mH for IIC, 8 mH for IIB
Switching output
Relay contact:
1 x voltage-free changeover contact
Contact rating:
Max. AC 250 V, 2 A
Response delay
None
Intrinsic safety
EX II (1)G [Ex ia Ga] IIC
Housing
Wall mounting housing made of impact-resistant plastic (ABS)
W x H x D:
100 x 188 x 65 mm
Degree of protection:
IP 30 (EN 60529)