Transducer NB 220 H for overfill prevention system (WHG)

AFRISO Messumformer NB 220 H DC 24V VOR 91770 91780 object_image_56302imagemain_en AFRISO Messumformer NB 220 H DC 24V VOR 91770 91780 object_image_56302imagemain_en
Messumformer NB 220 H DC 24V
AFRISO Messumformer NB 220 H DC 24V VOR 91770 91780 object_image_56302imagemain_en
AFRISO Messumformer NB 220 H DC 24V SAL 91770 91780 AFRISO Messumformer NB 220 H DC 24V SAL 91770 91780
Messumformer NB 220 H DC 24V
AFRISO Messumformer NB 220 H DC 24V SAL 91770 91780
AFRISO Messumformer NB 220 H DC 24V SAR 91770 91780 AFRISO Messumformer NB 220 H DC 24V SAR 91770 91780
Messumformer NB 220 H DC 24V
AFRISO Messumformer NB 220 H DC 24V SAR 91770 91780
AFRISO Messumformer NB 220 H DC 24V VOR 91770 91780 object_image_56302imagemain_en
AFRISO Messumformer NB 220 H DC 24V SAL 91770 91780
AFRISO Messumformer NB 220 H DC 24V SAR 91770 91780
Data sheet Transducer NB 220 H for overfill prevention system (WHG)
AFRISO Data sheet Transducer NB 220 H for overfill prevention system (WHG)

Versions

Part no. Remember
Transducer NB 220 H DC 24 V 53219
Transducer NB 220 H AC 230 V 53210

Blue part no. = in-stock items

Description Format Language Download / Link
Data sheet Transducer NB 220 H for overfill prevention system (WHG) Data sheet PDF
AFRISO Data sheet Transducer NB 220 H for overfill prevention system (WHG)
Type-approved together with all level probes type series 76 as part of an overfill prevention system. When the level probe comes in contact with the liquid, the relay switches. Alarm units for visual and audible alarms are additionally required.
Operating temperature range
Ambient:
-20/+60 °C
Storage:
-25/+60 °C
Supply voltage
DC 24 V or AC 230 V
Nominal power
Max. 6 W, max. 4 VA
Switching output
Relay contact:
1 x voltage-free changeover contact
Contact rating:
Max. AC 250 V, 4 A, 500 VA
Max. DC 250 V, 0.25 A, 50 W
Housing
Plug-in housing
W x H x D:
50 x 110 x 110 mm
Degree of protection:
IP 30 (EN 60529)
Approval
DIBt: Z-65.11-193