CAPBs® extension set valve balancing

AFRISO CAPBs Ergänzungsset Ventilabgleich VOR 3270 object_image_90187imagemain_en AFRISO CAPBs Ergänzungsset Ventilabgleich VOR 3270 object_image_90187imagemain_en
CAPBs Ergänzungsset Ventilabgleich
AFRISO CAPBs Ergänzungsset Ventilabgleich VOR 3270 object_image_90187imagemain_en
AFRISO CAPBs Ergänzungsset Ventilabgleich VOR 3270 object_image_90187imagemain_en
Data sheet CAPBs® extension set valve balancing
AFRISO Data sheet CAPBs® extension set valve balancing

Versions

Part no. Remember
CAPBs® extension set valve balancing P00059

Blue part no. = in-stock items

Description Format Language Download / Link
Data sheet CAPBs® extension set valve balancing Data sheet PDF
AFRISO Data sheet CAPBs® extension set valve balancing
Extension set in system case S to extend the CAPBs® set line balancing to measure the differential pressure of VarioQ valves and lockshield valves to adjust the flow rate at radiators during hydraulic balancing. The free app EuroSoft live facilitates the measurement with step-by-step operation of the measuring system. All standard AFRISO VarioQ/-DP valves are stored in the app. The valve data can also be entered manually. The water volumes can be easily set at the VarioQ valve without conversion.
Dimensions (W x H x D)
Sensor module:
42 x 80 x 35 mm
Case:
260 x 63 x 155 mm
Weight
95 g
Measuring range
-7/+7 bar
Accuracy
± 10 mbar (< 999.99 mbar)
± 1 % v. Mw. (> 1,000 mbar)
Resolution
0.1 mbar (< 999.99 mbar)
1 mbar (> 1,000 mbar)
Hose connection
2 x Connection piece DN 2.7
Scope of delivery
  • Pressure transmitter CAPBs<sup>®</sup> sens PT 85
  • Adjustment key for VarioQ und VarioQ-Kombi
  • Pre-adjustment key VarioQ
  • Measuring hose set for VarioQ ⌀ 4 mm (red and blue), 2 x measuring needle Q
  • Measuring needle drill, screwdriver and hex key 4 mm
  • Modular system case S